Load   Number of Ground Wires
SystemGround Material
Phase/Neutral ConductorGround TypeNEC Code
Wire InsulationMaximum Wire Size
Number of Phase WiresConduit Type
Number of Neutral WiresMaximum Conduit Size
Neutral Carrying ConductorNEC CodePower Factor

Load Summary: 283 kVA  |  400 Calcualted Amps  |  400 OverCurrent Amps


FeederLoad Amps Maximum Length
2% VD (5.5 V) 3% VD (8.3 V) 5% VD (13.8 V)
2 [(3#3/0Cu, 1#3/0Cu, 1#3Cu) 2" EMT] 100% Load (400 A) 146 feet219 feet366 feet
80% Load (320 A) 183 feet274 feet458 feet
Feeder: 2 [(3#3/0Cu, 1#3/0Cu, 1#3Cu) 2" EMT] Length
ft
Anticipated Load
A
Max Volt Drop
%
Actual
13.84 V (4.99%)

Notes:


1For horsepower calculation, motor powerfactor and efficiency are set at 0.90.
2For cooling ton calculation, no losses are figured in calculation.
3Voltage Drop is Line to Neutral Calculations and not Line to Line.

No guarantees are made as to the accuracy of the calculation or compliance with local codes.  Verify all calculations with a professional engineer. If you find an error, or have a suggestion, please send us an email.
Construction Monkey Product Explore Company
Construction Monkey was formed to fill a need in the Construction Industry that has been forming for several years. The industry has become increasingly dominated by General Contractors that subcontract more and more of the work and thus there are more subcontractors providing the real construction services on any given project. These subcontractors are burdened with the risk, performance, safety, quality, and management of the projects being built, while they are in a more competitive market space due to the nearly 800,000 specialty subcontractors in the US alone. The Monkey is here to help subcontractors perform at top levels in this difficult environment. Overview